About the product: Surge protection with integrated status indicator and disconnect knife for a 2-wire Ex i signal circuit with common reference potential.
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2906821 Phoenix Contact price in the box on the right side or send a quick quote.
2906821 Product Details
- Height 105.8 mm
- Permissible humidity (operation) 5 % ... 95 %
- IEC test classification C1
- Rated current 600 mA (40 °C)
- Total discharge current Itotal (8/20) µs 10 kA
- Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system typ. 960 kHz
- Surge protection fault message optical
- Tightening torque 0.5 Nm ... 0.6 Nm
- REACh SVHC Lead 7439-92-1
- ECLASS 4.0 27140201
- ECLASS 7.0 27130807
- ETIM 3.0 EC000943
- UNSPSC 7.0901 39121610
- UNSPSC 21.0 39121620
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Max. input current Ii 400 mA (T4 / ≤ 50 °C)
- Operating effective current IC at UC ≤ 5 µA
- Voltage protection level Up static (line-earth) ≤ 55 V (C1 - 1 kV/500 A)
- Response time tA (line-earth) ≤ 1 ns
- Pulse reset time (line-earth) ≤ 300 ms
- Screw thread M3
- Conductor cross section solid 0.2 mm² ... 4 mm²
- ECLASS 10.0.1 27130807
- ECLASS 5.1 27130801
- ETIM 6.0 EC000943
- UNSPSC 11 39121610
- Depth 83.5 mm (incl. DIN rail 7.5 mm)
- Maximum inner capacitance Ci negligible
- Max. internal inductance Li negligible
- Pulse discharge current Iimp (10/350) µs (line-earth) 0.5 kA
- Capacity (line-earth) typ. 2.2 nF
- Impulse durability (line-earth) C1 - 1 kV / 500 A
- Stripping length 8 mm
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.1 27130801
- ECLASS 9.0 27130807
- ETIM 4.0 EC000943
- UNSPSC 12.01 39121610
- Ambient temperature (operation) -40 °C ... 35 °C (T6 / 85 °C)
- Degree of protection IP20
- Maximum continuous voltage UC 30 V DC
- Nominal discharge current In (8/20) µs (line-earth) 5 kA
- Voltage protection level Up (line-earth) ≤ 140 V (C1 - 1 kV/500 A)
- Resistance per path 1.65 Ω ±20 %
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Standards/specifications EN 60079-0 2012 + A11:2013
- ECLASS 11.0 27130807
- ECLASS 5.0 27130801
- ETIM 7.0 EC000943
- UNSPSC 18.0 39121620
- Width 6.2 mm +0.1 mm
- Altitude ≤ 2000 m (amsl (above mean sea level))
- Max. input voltage Ui 30 V DC
- Nominal voltage UN 24 V DC
- Residual current IPE ≤ 10 µA
- Input attenuation aE, asym. typ. 0.3 dB (≤ 270 kHz/150 Ω)
- Max. required back-up fuse 630 mA (FF)
- Connection method Screw connection
- Conductor cross section AWG 24 ... 12
- UL, USA/Canada Class I, Div. 2, Groups A, B, C, D T4
- ECLASS 6.0 27130800
- ETIM 2.0 EC000943
- UNSPSC 6.01 30212010
- UNSPSC 19.0 39121620
- UNSPSC 13.2 39121620
- UNSPSC 20.0 39121620
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
2906821
Select Qty:
Average response time: 11 minutes
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨