Nikki Gonzales
Nick Goetz
Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

2906794 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2906794 Surge protection, consisting of protective plug and base element, with integrated status indicator and disconnect knife for two signal wires with common reference potential, e.g., Digital IN/OUT. Indirect grounding via gas-filled surge arrester.
Phoenix Contact

Part#:2906794

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: Surge protection, consisting of protective plug and base element, with integrated status indicator and disconnect knife for two signal wires with common reference potential, e.g., Digital IN/OUT. Indirect grounding via gas-filled surge arrester.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2906794 Phoenix Contact price in the box on the right side or send a quick quote.

2906794 Product Details

  • Depth
    100 mm (incl. DIN rail 7.5 mm)
  • Mounting type
    DIN rail: TH 35 - 7.5 mm
  • Nominal voltage UN
    24 V DC
  • Residual current IPE
    ≤ 1 µA
  • Pulse discharge current Iimp (10/350) µs (line-earth)
    0.5 kA
  • Response time tA (line-earth)
    ≤ 100 ns
  • Pulse reset time (line-earth)
    ≤ 30 ms
  • Conductor cross section solid
    0.2 mm² ... 4 mm²
  • ECLASS 4.0
    27140201
  • ECLASS 6.0
    27130800
  • ETIM 4.0
    EC000943
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Degree of protection
    IP20
  • IEC test classification
    C1
  • Rated current
    600 mA (56 °C)
  • Total discharge current Itotal (8/20) µs
    10 kA
  • Voltage protection level Up static (line-earth)
    ≤ 750 V (C1 - 1 kV/500 A)
  • Capacity (line-signalground)
    typ. 2.2 nF
  • Max. required back-up fuse
    630 mA (FF)
  • Max. total discharge current I total max (8/20) µs
    20 kA (1x)
  • Standards/specifications
    IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 5.0
    27130801
  • ECLASS 5.1
    27130801
  • ETIM 7.0
    EC000943
  • UNSPSC 12.01
    39121610
  • UNSPSC 20.0
    39121620
  • Ambient temperature (operation)
    -40 °C ... 85 °C
  • Permissible humidity (operation)
    5 % ... 95 %
  • Direction of action
    Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
  • Operating effective current IC at UC
    ≤ 5 µA
  • Pulse discharge current Iimp (10/350) µs (line-signalground)
    0.5 kA
  • Voltage protection level Up (line-signalground)
    ≤ 140 V (C1 - 1 kV/500 A)
  • Response time tA (line-signalground)
    ≤ 1 ns
  • Impulse durability (line-earth)
    C1 - 1 kV / 500 A
  • Impulse durability (line-signalground)
    C1 - 1 kV / 500 A
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • ECLASS 10.0.1
    27130807
  • ECLASS 7.0
    27130807
  • UNSPSC 6.01
    30212010
  • UNSPSC 19.0
    39121620
  • Height
    105.8 mm
  • Altitude
    ≤ 4000 m (amsl (above mean sea level))
  • Color
    traffic grey A RAL 7042
  • Maximum continuous voltage UC
    30 V DC
  • Nominal discharge current In (8/20) µs (line-signal ground)
    5 kA
  • Voltage protection level Up (line-earth)
    ≤ 750 V (C1 - 1 kV/500 A)
  • Input attenuation aE, asym.
    typ. 0.3 dB (≤ 270 kHz/150 Ω)
  • Resistance per path
    1.65 Ω ±20 %
  • Pulse reset time (line-signalground)
    ≤ 300 ms
  • Stripping length
    8 mm
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 11.0
    27130807
  • ECLASS 9.0
    27130807
  • ETIM 2.0
    EC000943
  • ETIM 6.0
    EC000943
  • UNSPSC 18.0
    39121620
  • Width
    6.2 mm +0.1 mm
  • Housing material
    PBT
  • Flammability rating according to UL 94
    V-0
  • Type
    DIN rail module, two-section, divisible
  • Nominal discharge current In (8/20) µs (line-earth)
    5 kA
  • Voltage protection level Up static (line-signalground)
    ≤ 55 V (C1 - 1 kV/500 A)
  • Cut-off frequency fg (3 dB), asym. (signal ground) in 150 Ω system
    typ. 960 kHz
  • Connection method
    Push-in connection
  • Conductor cross section AWG
    24 ... 12
  • ECLASS 4.1
    27130801
  • ETIM 3.0
    EC000943
  • UNSPSC 7.0901
    39121610
  • UNSPSC 13.2
    39121620
  • UNSPSC 11
    39121610
  • UNSPSC 21.0
    39121620

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2906794

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo