2906062 Phoenix Contact Electrical Safety Devices

Phoenix Contact 2906062 Hybrid motor starter for starting 3~ AC motors up to 550 V AC, with 24 V DC input, 2.4 A output current, emergency stop function, adjustable overload shutdown, higher transient voltage strength, and push-in connection.
Phoenix Contact

Part#:2906062

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

Hybrid motor starter for starting 3~ AC motors up to 550 V AC, with 24 V DC input, 2.4 A output current, emergency stop function, adjustable overload shutdown, higher transient voltage strength, and push-in connection.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2906062 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Depth
    114 mm
  • Type of protection
    Surge protection
  • Rated actuating voltage UC
    24 V DC
  • Output name
    Acknowledge output
  • Load current range
    180 mA ... 2.4 A (see to derating)
  • Note
    Confirmation: floating change-over contact, signal contact
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Input name
    Control input
  • Switching threshold
    9.6 V (“0” signal)
  • Typical turn-off time
    < 30 ms
  • Rated operating current Ie
    2.4 A (AC-51)
  • Leakage current
    0 mA
  • Mounting position
    vertical (horizontal DIN rail, motor output below)
  • Switching capacity according to IEC 60947-5-1
    3 A (230 V, AC15)
  • Assembly instructions
    alignable, for spacing see derating
  • Indication
    Red LED
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Standards/regulations
    IEC 60947-1
  • Insulation
    Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
  • Additional text
    Safe shutdown
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 10.0.1
    27370905
  • ECLASS 5.1
    27024000
  • ETIM 2.0
    EC001037
  • ETIM 3.0
    EC001037
  • UNSPSC 13.2
    25173902
  • Width
    22.5 mm
  • Maximum altitude
    ≤ 2000 m
  • Rated control supply current IS
    40 mA
  • Rated actuating current IC
    5 mA
  • ECLASS 4.1
    27021100
  • ETIM 4.0
    EC001037
  • UNSPSC 18.0
    25173902
  • UNSPSC 21.0
    25173902
  • Height
    107.5 mm
  • Degree of protection
    IP20
  • Control supply voltage range
    19.2 V DC ... 30 V DC
  • Triggering voltage range
    19.2 V DC ... 30 V DC
  • Rated operating voltage Ue
    500 V AC
  • Mains frequency
    50/60 Hz
  • Cooling time
    20 min.
  • Motor starter type
    Direct starter
  • Operating mode
    100% operating factor
  • Minimum power dissipation
    1.1 W
  • Operating voltage display
    Green LED
  • Conductor cross section AWG
    24 ... 14
  • Rated insulation voltage
    500 V
  • Overvoltage category
    III
  • FLA
    2.4 A (480 V AC)
  • ECLASS 11.0
    27370905
  • Category code
    NLDX / NRNT
  • ECLASS 7.0
    27024002
  • Ambient temperature (operation)
    5 °C ... 70 °C (observe derating)
  • Rated control circuit supply voltage US
    24 V DC
  • Switching level
    < 5 V DC (For EMERGENCY STOP)
  • Operating voltage range
    42 V AC ... 550 V AC
  • Trigger characteristic in acc. with IEC 60947-4-2
    Class 10A
  • Contact type
    1 changeover contact
  • Mounting type
    DIN rail mounting
  • Status display
    Yellow LED
  • Stripping length
    10 mm
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Degree of pollution
    2
  • Designation
    Category (ISO 13849)
  • Identification
    ≤ 3
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 5.0
    27024000
  • ECLASS 9.0
    27370905
  • ETIM 6.0
    EC001037
  • UNSPSC 20.0
    25173902
  • Switching frequency
    ≤ 2 Hz (Load-dependent)
  • Maximum power dissipation
    3.3 W
  • Connection name
    Load circuit
  • Connection method
    Push-in connection
  • Rated surge voltage
    6 kV
  • Certificate
    NLDX.E228652
  • SCCR
    100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
  • Group installation
    20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
  • ECLASS 4.0
    27021100
  • ECLASS 6.0
    27024000
  • ETIM 7.0
    EC001037
  • UNSPSC 19.0
    25173902

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo