2905155 Phoenix Contact Electrical Safety Devices

Phoenix Contact 2905155 Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC, output current: 3 A, emergency stop function, adjustable overload shutdown, and screw connection, DIN rail connector provided.
Phoenix Contact

Part#:2905155

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC, output current: 3 A, emergency stop function, adjustable overload shutdown, and screw connection, DIN rail connector provided.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2905155 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Motor starter type
    Direct starter
  • Assembly instructions
    alignable, for spacing see derating
  • Status display
    Yellow LED
  • Stripping length
    8 mm
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Rated surge voltage
    6 kV
  • Standards/regulations
    IEC 60947-1
  • Certificate
    NLDX.E228652
  • Group installation
    20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
  • ECLASS 10.0.1
    27370905
  • ECLASS 4.0
    27021100
  • ECLASS 6.0
    27024000
  • ETIM 3.0
    EC001037
  • ETIM 4.0
    EC001037
  • ETIM 7.0
    EC001037
  • Depth
    114 mm
  • Ambient temperature (operation)
    -5 °C ... 60 °C (observe derating)
  • Type of protection
    Surge protection
  • Note
    The enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3 ms duration),unblanking pulses of max. 4 ms are tolerated without adversely affecting the safety function.
  • Operating voltage range
    42 V AC ... 550 V AC
  • Output name
    AC output
  • Cooling time
    20 min. (for auto reset)
  • Mounting position
    vertical (horizontal DIN rail, motor output below)
  • Operating voltage display
    Green LED
  • Screw thread
    M3
  • Overvoltage category
    III
  • Additional text
    Safe shutdown
  • Category code
    NLDX / NRNT
  • ECLASS 5.0
    27024000
  • ETIM 6.0
    EC001037
  • UNSPSC 18.0
    25173902
  • Height
    107 mm
  • Degree of protection
    IP20
  • Control supply voltage range
    19.2 V DC ... 30 V DC
  • Rated actuating voltage UC
    24 V DC
  • Switching level
    < 5 V DC (For EMERGENCY STOP)
  • Rated operating current Ie
    3 A (AC-51)
  • Trigger characteristic in acc. with IEC 60947-4-2
    Class 10
  • Mains frequency
    50/60 Hz
  • Leakage current
    0 mA
  • Operating mode
    100% operating factor
  • Connection name
    Load circuit
  • Indication
    Red LED
  • Torque
    0.5 Nm ... 0.6 Nm
  • Insulation
    Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
  • Identification
    ≤ 3
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 11.0
    27370905
  • ECLASS 7.0
    27024002
  • ETIM 2.0
    EC001037
  • UNSPSC 20.0
    25173902
  • Width
    22.5 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Rated control supply current IS
    60 mA
  • Triggering voltage range
    19.2 V DC ... 30 V DC
  • Typical turn-off time
    < 30 ms
  • Rated operating voltage Ue
    500 V AC
  • Response time
    < 0.5 s
  • Mounting type
    DIN rail mounting
  • Maximum power dissipation
    4.1 W
  • Connection method
    Screw connection
  • Conductor cross section AWG
    24 ... 14
  • Rated insulation voltage
    550 V
  • Designation
    Category (ISO 13849)
  • FLA
    3 A (480 V AC)
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 4.1
    27021100
  • ECLASS 5.1
    27024000
  • UNSPSC 13.2
    25173902
  • UNSPSC 21.0
    25173902
  • Maximum altitude
    ≤ 2000 m
  • Rated control circuit supply voltage US
    24 V DC
  • Input name
    Enable input
  • Rated actuating current IC
    7 mA
  • Switching threshold
    9.6 V (“0” signal)
  • Load current range
    180 mA ... 3 A (see to derating)
  • Operate threshold
    > 33 A
  • Switching frequency
    ≤ 2 Hz (Load-dependent)
  • Minimum power dissipation
    0.88 W
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Degree of pollution
    2
  • SCCR
    100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
  • Horsepower ratings
    0.5 hp (208 V AC)
  • ECLASS 9.0
    27370905
  • UNSPSC 19.0
    25173902

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo