2905154 Phoenix Contact Electrical Safety Devices

Phoenix Contact 2905154 Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC, output current: 0.6 A, emergency stop function, adjustable overload shutdown, and screw connection, DIN rail connector provided.
Phoenix Contact

Part#:2905154

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC, output current: 0.6 A, emergency stop function, adjustable overload shutdown, and screw connection, DIN rail connector provided.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2905154 Phoenix Contact price in the box on the right side or send a quick quote.

2905154 Product Details

  • Height
    107 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Rated control supply current IS
    60 mA
  • Note
    The enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3 ms duration),unblanking pulses of max. 4 ms are tolerated without adversely affecting the safety function.
  • Rated actuating current IC
    7 mA
  • Output name
    AC output
  • Leakage current
    0 mA
  • Mounting position
    vertical (horizontal DIN rail, motor output below)
  • Operating mode
    100% operating factor
  • Minimum power dissipation
    0.88 W
  • Connection method
    Screw connection
  • Rated insulation voltage
    550 V
  • Overvoltage category
    III
  • FLA
    0.6 A (480 V AC)
  • ETIM 2.0
    EC001037
  • UNSPSC 19.0
    25173902
  • Input name
    Enable input
  • Triggering voltage range
    19.2 V DC ... 30 V DC
  • Switching threshold
    9.6 V (“0” signal)
  • Load current range
    75 mA ... 600 mA (see to derating)
  • Trigger characteristic in acc. with IEC 60947-4-2
    Class 10
  • Switching frequency
    ≤ 2 Hz (Load-dependent)
  • Assembly instructions
    alignable, for spacing see derating
  • Operating voltage display
    Green LED
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Degree of pollution
    2
  • Identification
    ≤ 3
  • SCCR
    100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 4.0
    27021100
  • ECLASS 7.0
    27024002
  • UNSPSC 13.2
    25173902
  • Ambient temperature (operation)
    -5 °C ... 60 °C (observe derating)
  • Type of protection
    Surge protection
  • Switching level
    < 5 V DC (For EMERGENCY STOP)
  • Mains frequency
    50/60 Hz
  • Cooling time
    20 min. (for auto reset)
  • Mounting type
    DIN rail mounting
  • Connection name
    Load circuit
  • Conductor cross section AWG
    24 ... 14
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Insulation
    Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
  • Standards/regulations
    IEC 60947-1
  • Group installation
    20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
  • ECLASS 10.0.1
    27370905
  • ECLASS 6.0
    27024000
  • ETIM 3.0
    EC001037
  • UNSPSC 18.0
    25173902
  • Depth
    114 mm
  • Degree of protection
    IP20
  • Rated actuating voltage UC
    24 V DC
  • Rated operating voltage Ue
    500 V AC
  • Operate threshold
    > 10 A
  • Response time
    < 0.5 s
  • Status display
    Yellow LED
  • Screw thread
    M3
  • Torque
    0.5 Nm ... 0.6 Nm
  • Rated surge voltage
    6 kV
  • Certificate
    NLDX.E228652
  • Category code
    NLDX / NRNT
  • ECLASS 11.0
    27370905
  • ECLASS 5.0
    27024000
  • ECLASS 9.0
    27370905
  • ETIM 4.0
    EC001037
  • UNSPSC 21.0
    25173902
  • Width
    22.5 mm
  • Maximum altitude
    ≤ 2000 m
  • Rated control circuit supply voltage US
    24 V DC
  • Control supply voltage range
    19.2 V DC ... 30 V DC
  • Typical turn-off time
    < 30 ms
  • Operating voltage range
    42 V AC ... 550 V AC
  • Rated operating current Ie
    0.6 A (AC-51)
  • Motor starter type
    Direct starter
  • Maximum power dissipation
    2.5 W
  • Indication
    Red LED
  • Stripping length
    8 mm
  • Designation
    Category (ISO 13849)
  • Additional text
    Safe shutdown
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.1
    27021100
  • ECLASS 5.1
    27024000
  • ETIM 6.0
    EC001037
  • ETIM 7.0
    EC001037
  • UNSPSC 20.0
    25173902

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2905154

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo