2838539 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2838539 LSA-PLUS plug (COMTRAB CTM) for floating signal circuits, for protecting a double wire from analog and digital telecommunications interfaces (up to 50 Mbps). Nominal voltage: 110 V AC
Phoenix Contact

Part#:2838539

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Checking verified in-stock parts...

About the product: LSA-PLUS plug (COMTRAB CTM) for floating signal circuits, for protecting a double wire from analog and digital telecommunications interfaces (up to 50 Mbps). Nominal voltage: 110 V AC

About the manufacturer: Phoenix Contact develops and manufactures industrial electrical and electronic technology products that power, protect, connect and automate systems and equipment.

Check out the 2838539 Phoenix Contact price in the box on the right side or send a quick quote.

2838539 Product Details

  • Width
    9.4 mm
  • Degree of protection
    IP20
  • Mounting type
    On CT-TERMIBLOCK and LSA-PLUS disconnect strip
  • Arrester can be tested with CHECKMASTER from software version:
    From SW rev. 1.10
  • Nominal voltage UN
    110 V AC
  • Residual current IPE
    ≤ 2 µA (per path)
  • Pulse discharge current Iimp (10/350) µs (line-earth)
    1 kA
  • Ambient temperature (operation)
    -25 °C ... 75 °C
  • Housing material
    PA 6.6
  • Color
    jet black RAL 9005
  • Transmission speed
    42 Mbps
  • IEC test classification
    B2
  • Operating effective current IC at UC
    ≤ 5 µA (in the signal circuit)
  • Nominal discharge current In (8/20) µs (line-line)
    5 kA
  • Output voltage limitation at 1 kV/µs (line-line) spike
    ≤ 260 V
  • Voltage protection level Up (line-line)
    ≤ 260 V (C2 - 10 kV / 5 kA)
  • Response time tA (line-earth)
    ≤ 100 ns
  • Capacity (line-line)
    typ. 100 pF
  • Max. required back-up fuse
    150 mA (T/IEC 60127-2/3)
  • Connection method IN
    COMTRAB plug-in system
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.1
    27130800
  • ECLASS 5.1
    27130800
  • ECLASS 9.0
    27130807
  • ETIM 4.0
    EC000943
  • UNSPSC 11
    39121610
  • UNSPSC 19.0
    39121620
  • Height
    21 mm
  • Altitude
    ≤ 2000 m (amsl (above mean sea level))
  • Degree of pollution
    2
  • Type
    LSA-PLUS module
  • Maximum continuous voltage UC
    60 V DC
  • Nominal discharge current In (8/20) µs (line-earth)
    5 kA
  • Nominal pulse current Ian (10/1000) µs (line-earth)
    100 A
  • Residual voltage with Ian (10/1000) µs (line-line)
    ≤ 10 V
  • Voltage protection level Up (line-earth)
    ≤ 800 V (C2 - 10 kV / 5 kA)
  • Voltage protection level Up static (line-earth)
    ≤ 60 V (C2 - 10 kV / 5 kA)
  • Cut-off frequency fg (3 dB), sym. in 100 Ω system
    typ. 20 MHz
  • Surge protection fault message
    none
  • Connection method
    Spring contact
  • Connection method OUT
    COMTRAB plug-in system
  • ECLASS 10.0.1
    27130807
  • ECLASS 7.0
    27130807
  • ETIM 3.0
    EC000943
  • UNSPSC 6.01
    30212010
  • UNSPSC 13.2
    39121620
  • Depth
    52.4 mm
  • Flammability rating according to UL 94
    V-0
  • Overvoltage category
    II
  • Direction of action
    Line-Line & Line-Earth Ground
  • Rated current
    380 mA AC (25 °C)
  • Total discharge current Itotal (8/20) µs
    10 kA
  • Total discharge current Itotal (10/350) µs
    2.5 kA
  • Residual voltage at In (line-line)
    ≤ 10 V
  • Residual voltage at In (line-earth)
    ≤ 55 V
  • Response time tA (line-line)
    ≤ 1 ns
  • Resistance per path
    3.3 Ω 20 %
  • Impulse durability (line-line)
    B2 - 4 kV / 100 A
  • Connection technology
    LSA-PLUS
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • ECLASS 5.0
    27130800
  • ECLASS 6.0
    27130800
  • ETIM 2.0
    EC000943
  • ETIM 7.0
    EC000943
  • UNSPSC 20.0
    39121620
  • UNSPSC 21.0
    39121620
  • Nominal pulse current Ian (10/1000) µs (line-line)
    100 A
  • Output voltage limitation at 1 kV/µs (line-earth) spike
    ≤ 800 V
  • Residual voltage with Ian (10/1000) µs (line-earth)
    ≤ 12 V
  • Voltage protection level Up static (line-line)
    ≤ 10 V (C2 - 10 kV / 5 kA)
  • Input attenuation aE, sym.
    typ. 0.3 dB (≤ 1.8 MHz/100 Ω)
  • Alternating current carrying capacity (line-earth)
    5 A - 1 s
  • Impulse durability (line-earth)
    B2 - 4 kV / 100 A
  • Standards/specifications
    IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
  • ECLASS 11.0
    27130807
  • ECLASS 4.0
    27130800
  • ETIM 6.0
    EC000943
  • UNSPSC 7.0901
    39121610
  • UNSPSC 12.01
    39121610
  • UNSPSC 18.0
    39121620

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

Shipping and Delivery Worldwide

calculate cost and time at Checkout


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo