2800918 Phoenix Contact Electrical Circuit Protection & Load Centers
Part#:2800918
Manufacturer:Phoenix Contact
Product Lifecycle:Active
Checking verified in-stock parts...
About the product: Electronic circuit breaker, 1-pos., active current limitation, 1 N/C contact, plug for base element.
About the manufacturer: Phoenix Contact develops and manufactures industrial electrical and electronic technology products that power, protect, connect and automate systems and equipment.
Check out the 2800918 Phoenix Contact price in the box on the right side or send a quick quote.
2800918 Product Details
- Number of positions 1
- Complete module height 90 mm
- Installation instructions When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).Special precautionary measures must be taken in systems or mac
- Depth 52 mm
- Humidity test 96 h, 95 % RH, 40 °C
- Degree of protection IP30 (Actuation area)
- Color gray
- Operating voltage 24 V DC
- Closed circuit current I0 typ. 8 mA (When switched on)
- Auxiliary type of contact floating signal contact
- Maximum auxiliary contact operating voltage 30 V DC
- Standards/specifications EMV EN 61000-6-3 Interference emission
- ECLASS 11.0 27140401
- ECLASS 4.0 27141100
- UNSPSC 6.01 30211812
- UNSPSC 18.0 39121410
- Complete module width 12.3 mm
- Ambient temperature (storage/transport) -40 °C ... 70 °C
- Mounting type on base element
- Nominal current IN 4 A
- Required backup fuse not required, integrated failsafe element
- Shutdown time load circuit 200 ms (see time/current characteristic curve)
- Max. capacitive load load circuit 20000 µF
- REACh SVHC Lead 7439-92-1
- ECLASS 5.0 27141100
- ETIM 3.0 EC000899
- ETIM 7.0 EC000899
- UNSPSC 11 39121411
- Width 12.3 mm
- Ambient temperature (operation) -25 °C ... 50 °C (non-condensing)
- Flammability rating according to UL 94 V-0
- Type Male
- Active current limitation typ. 1.25 x IN
- Temperature derating 4 A (at 50 °C)
- Dielectric strength max. 30 V DC (Load circuit)
- Minimum auxiliary contact operating voltage 10 V DC
- Designation Shipbuilding approval
- ECLASS 10.0.1 27140401
- ECLASS 6.0 27141100
- ECLASS 9.0 27141116
- UNSPSC 13.2 39121410
- UNSPSC 21.0 39121410
- Height 45 mm
- Complete module depth 77.3 mm
- Vibration (operation) 3g (according to IEC 60068-2-6, Test Fc)
- Degree of pollution 2
- Rated surge voltage 0.5 kV
- Power dissipation 0.81 W (Nominal operation)
- Voltage drop 100 mV (at IN)
- Maximum auxiliary contact operating current 0.5 A
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.1 27141100
- ETIM 4.0 EC000899
- UNSPSC 12.01 39121411
- UNSPSC 20.0 39121410
- Fuse type electronic
- Tripping method E (electronic)
- Undervoltage switch-off load circuit < 14 V (typ. OFF)
- Minimum auxiliary contact operating current 10 mA
- Identification DNV GL
- ECLASS 5.1 27141100
- ECLASS 7.0 27141116
- ETIM 6.0 EC000899
- UNSPSC 7.0901 39121411
- UNSPSC 19.0 39121410
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
Shipping and Delivery Worldwide
calculate cost and time at Checkout
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨