2800912 Phoenix Contact Electrical Circuit Protection & Load Centers
Part#:2800912
Manufacturer:Phoenix Contact
Product Lifecycle:Active
Get a quick Quote!
About the product: Electronic circuit breaker, 1-pos., active current limitation, status output and reset input, plug for base element.
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Circuit Protection & Load Centers that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2800912 Phoenix Contact price in the box on the right side or send a quick quote.
2800912 Product Details
- Complete module width 12.3 mm
- Mounting type on base element
- Degree of pollution 2
- Operating voltage 24 V DC
- Tripping method E (electronic)
- Height 45 mm
- Ambient temperature (storage/transport) -40 °C ... 70 °C
- Complete module depth 77.3 mm
- Color gray
- Type Male
- Power dissipation 1.04 W (Nominal operation)
- Dielectric strength max. 30 V DC (Load circuit)
- Undervoltage switch-off load circuit < 14 V (typ. OFF)
- Current consumption reset input typ. 2.6 mA (at 24 V DC)
- ECLASS 11.0 27140401
- ECLASS 7.0 27141116
- Complete module height 90 mm
- Vibration (operation) 3g (according to IEC 60068-2-6, Test Fc)
- Flammability rating according to UL 94 V-0
- Rated surge voltage 0.5 kV
- Closed circuit current I0 typ. 8 mA (When switched on)
- Shutdown time load circuit 130 ms (see time/current characteristic curve)
- Required backup fuse not required, integrated failsafe element
- Output current status output max. 0.2 A (Short-circuit-proof)
- Auxiliary type of contact Positive-switching signal output
- Identification DNV GL
- Width 12.3 mm
- Ambient temperature (operation) -25 °C ... 50 °C (non-condensing)
- Humidity test 96 h, 95 % RH, 40 °C
- Installation instructions When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).Special precautionary measures must be taken in systems or mac
- Nominal current IN 6 A
- Temperature derating 5 A (at 50 °C)
- Output voltage status output 24 V DC
- Pulse length reset input min. 20 ms
- Standards/specifications EMV EN 61000-6-3 Interference emission
- ECLASS 10.0.1 27140401
- ECLASS 4.0 27141100
- ETIM 4.0 EC000899
- ETIM 7.0 EC000899
- UNSPSC 12.01 39121411
- Depth 52 mm
- Degree of protection IP30 (Actuation area)
- Number of positions 1
- Fuse type electronic
- Active current limitation typ. 1.25 x IN
- Voltage drop 130 mV (at IN)
- Voltage reset input < 3 V DC (Low state)
- REACh SVHC Lead 7439-92-1
- ECLASS 4.1 27141100
- ETIM 6.0 EC000899
- UNSPSC 13.2 39121410
- UNSPSC 19.0 39121410
- Max. capacitive load load circuit 20000 µF
- Input voltage reset input 7 V DC ... 30 V DC (Reset with falling edge)
- Designation Shipbuilding approval
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 5.0 27141100
- ECLASS 9.0 27141116
- UNSPSC 7.0901 39121411
- UNSPSC 21.0 39121410
- ECLASS 6.0 27141100
- ETIM 3.0 EC000899
- UNSPSC 6.01 30211812
- UNSPSC 18.0 39121410
- UNSPSC 20.0 39121410
- ECLASS 5.1 27141100
- UNSPSC 11 39121411
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
2800912
Select Qty:
Average response time: 11 minutes
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨