2701498 Phoenix Contact Programmable Logic Controllers

Phoenix Contact 2701498 Axioline E, Digital input device, PROFIBUS DP, M12 fast connection technology, Digital inputs: 16, 24 V DC, connection method: 4-conductor, Plastic housing, degree of protection: IP65/IP67
Phoenix Contact

Part#:2701498

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: Axioline E, Digital input device, PROFIBUS DP, M12 fast connection technology, Digital inputs: 16, 24 V DC, connection method: 4-conductor, Plastic housing, degree of protection: IP65/IP67

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Programmable Logic Controllers that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2701498 Phoenix Contact price in the box on the right side or send a quick quote.

2701498 Product Details

  • Supply voltage range
    18 V DC ... 31.2 V DC (including all tolerances, including ripple)
  • Number of inputs
    16
  • Protective circuit
    Overload protection, short-circuit protection of sensor supply
  • Width
    60 mm
  • Ambient temperature (operation)
    -25 °C ... 60 °C
  • Mounting type
    Wall mounting
  • Connection method
    M12 connector, double occupancy
  • Transmission speed
    9.6 kbps ... 12 Mbps (Automatic baud rate detection)
  • Depth
    30.5 mm
  • Ambient temperature (storage/transport)
    -25 °C ... 85 °C
  • Connection technology
    4-conductor
  • Air pressure (storage/transport)
    70 kPa ... 106 kPa (up to 3000 m above sea level)
  • Color
    anthracite
  • Note on the connection method
    B-coded
  • Transmission physics
    PROFIBUS-DP-compliant copper cable
  • Supply voltage
    24 V DC
  • Test section
    24 V supply (communications power and sensor supply, digital inputs)/bus connection 500 V AC 50 Hz 1 min.
  • REACh SVHC
    Lead 7439-92-1
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ETIM 2.0
    EC001433
  • System-specific protocols
    PROFIBUS protocols DP V1
  • Input name
    Digital inputs
  • Nominal input current at UIN
    typ. 3 mA
  • Immunity to ESD
    Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
  • Note on dimensions
    The height is 212 mm including fixing clips.
  • Permissible humidity (storage/transport)
    5 % ... 95 %
  • Housing material
    Pocan®
  • Address area assignment
    1 ... 126, adjustable
  • Mechanical tests
    Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
  • ECLASS 5.1
    27242600
  • ETIM 4.0
    EC001599
  • UNSPSC 11
    39121311
  • UNSPSC 7.0901
    43201404
  • Height
    185 mm
  • Permissible humidity (operation)
    5 % ... 95 %
  • Net weight
    480 g
  • Number
    2
  • Equipment type
    PROFIBUS slave
  • Number of positions
    4
  • Description of the input
    EN 61131-2 types 1 and 3
  • Input filter time
    < 1000 µs
  • Input voltage range "0" signal
    0 V ... 5 V DC
  • Input voltage range "1" signal
    11 V DC ... 30 V DC
  • Immunity to surge
    Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
  • ECLASS 4.0
    27240400
  • ECLASS 11.0
    27242604
  • ECLASS 9.0
    27242604
  • ETIM 7.0
    EC001599
  • UNSPSC 13.2
    32151602
  • ECLASS 5.0
    27242200
  • Drill hole spacing
    198.5 mm
  • Air pressure (operation)
    70 kPa ... 106 kPa (up to 3000 m above sea level)
  • Degree of protection
    IP65/IP67
  • Designation
    Actuators (UA) for additional devices
  • Designation connection point
    Copper cable
  • Current consumption
    typ. 3 mA ±15 % (at 24 V DC)
  • Nominal input voltage UIN
    24 V DC
  • Cable length
    max. 30 m (To the sensor)
  • Immunity to conducted interference
    Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
  • Immunity to EF
    Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • ECLASS 10.0.1
    27242604
  • ECLASS 7.0
    27242604
  • Protection class
    III (IEC 61140, EN 61140, VDE 0140-1)
  • ECLASS 4.1
    27240400
  • ECLASS 6.0
    27242600
  • ETIM 6.0
    EC001599
  • UNSPSC 6.01
    43172015
  • UNSPSC 21.0
    32151602
  • Interference emission
    Noise emission test as per EN 61000-6-4 Class A
  • Immunity to burst
    Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
  • UNSPSC 18.0
    32151602
  • UNSPSC 20.0
    32151602
  • ETIM 3.0
    EC001599
  • UNSPSC 12.01
    39121311
  • UNSPSC 19.0
    32151602

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2701498

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo