2701141 Phoenix Contact Programmable Logic Controllers

Phoenix Contact 2701141 Inline controller for use under harsh ambient conditions, with Ethernet interface for coupling to other controllers and systems, with programming options according to IEC 61131-3, complete with connector and labeling field.
Phoenix Contact

Part#:2701141

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Checking verified in-stock parts...

About the product: Inline controller for use under harsh ambient conditions, with Ethernet interface for coupling to other controllers and systems, with programming options according to IEC 61131-3, complete with connector and labeling field.

About the manufacturer: Phoenix Contact develops and manufactures industrial electrical and electronic technology products that power, protect, connect and automate systems and equipment.

Check out the 2701141 Phoenix Contact price in the box on the right side or send a quick quote.

2701141 Product Details

  • Immunity to ESD
    Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
  • Permissible humidity (storage/transport)
    10 % ... 95 % (according to DIN EN 61131-2)
  • ECLASS 4.1
    27240400
  • Immunity to EF
    Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
  • Vibration (operation)
    5g
  • UNSPSC 7.0901
    43201404
  • Program memory
    256 kByte
  • Number of control tasks
    8
  • UNSPSC 11
    43172018
  • UNSPSC 19.0
    39122114
  • REACh SVHC
    Lead 7439-92-1
  • Retentive mass storage
    8 kByte (NVRAM)
  • ECLASS 5.1
    27242700
  • ECLASS 6.0
    27242200
  • UNSPSC 18.0
    39122114
  • UNSPSC 13.2
    39122114
  • Air pressure (storage/transport)
    70 kPa ... 106 kPa (up to 3000 m above sea level)
  • Diagnostics tool
    DIAG+
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Mass storage
    256 kByte
  • Realtime clock
    Yes
  • Number
    1
  • Input name
    Digital inputs
  • Vibration (storage/transport)
    5g
  • Engineering tool
    PC WORX
  • ECLASS 4.0
    27240400
  • ECLASS 7.0
    27242207
  • ETIM 7.0
    EC000236
  • UNSPSC 12.01
    43201404
  • UNSPSC 20.0
    39122114
  • Degree of protection
    IP20
  • Programming languages supported
    Programming in acc. with IEC 61131-3
  • Processor
    Altera Nios II 64 MHz
  • ECLASS 11.0
    27242207
  • ETIM 6.0
    EC000236
  • ECLASS 9.0
    27242207
  • UNSPSC 6.01
    43172015
  • Number of devices with parameter channel
    max. 16
  • Device function
    PROFINET device
  • Output name
    Digital outputs
  • UNSPSC 21.0
    39122114
  • Residual ripple
    ± 5 %
  • Safety function
    No
  • Immunity to conducted interference
    Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
  • ECLASS 5.0
    27242700
  • ETIM 3.0
    EC001423
  • ETIM 4.0
    EC001596
  • Configuration tool
    Config+ Version 1.01 or later
  • Transmission speed
    max. 115.2 kbps
  • Number of inputs
    8
  • Air pressure (operation)
    70 kPa ... 106 kPa (up to 3000 m above sea level)
  • Number of supported branch terminals with remote bus branch
    max. 3
  • Power dissipation
    max. 5 W
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Typical current consumption
    210 mA
  • Depth
    71.5 mm
  • Height
    119.8 mm
  • Number of local bus devices that can be connected
    max. 63 (observe current consumption)
  • Width
    80 mm
  • Amount of process data
    max. 4096 Bit (INTERBUS)
  • Description of the input
    EN 61131-2 type 1 NPN/PNP
  • Connection technology
    2-, 3-, 4-conductor
  • Max. current consumption
    870 mA (370 mA communications power + 500 mA analog voltage supply)
  • Weight
    285 g
  • Interference emission
    Noise emission test as per EN 61000-6-4 EN 55011 Class A
  • Permissible humidity (operation)
    10 % ... 95 % (according to DIN EN 61131-2)
  • Controller redundancy
    No
  • Immunity to surge
    Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV
  • Ambient temperature (operation)
    -40 °C ... 60 °C
  • Shock
    25g, Criterion 1, according to IEC 60068-2-27
  • Number of supported devices
    max. 128
  • Connection method
    Spring-cage connection
  • Number of outputs
    4
  • Supply voltage
    24 V DC
  • ECLASS 10.0.1
    27242207
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • Immunity to burst
    Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, all interfaces 1 kVCriterion B, all interfaces 2 kV
  • Interface
    Parameterization/operation/diagnostics
  • Maximum output current per channel
    500 mA
  • Supply voltage range
    19.2 V DC ... 30 V DC
  • Diagnostics display
    No
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

Shipping and Delivery Worldwide

calculate cost and time at Checkout


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo