1923021 Phoenix Contact Terminal Blocks
Part#:1923021
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 2743
Nov 22, 2024
1-level terminal block with double connection on one side, cross section: 0.2 - 4 mm², AWG: 24 - 12, width: 6.2 mm, color: gray
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 1923021 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Short-time current 0.00048 kA
- Result of thermal test Test passed
- Short circuit stability result Test passed
- Test directions X-, Y- and Z-axis (pos. and neg.)
- Conductor cross section solid min. 0.2 mm²
- Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
- Shock duration 18 ms
- UNSPSC 12.01 39121410
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum 1.5 mm²
- Ambient temperature (actuation) -5 °C ... 70 °C
- ECLASS 5.0 27141100
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum 0.5 mm²
- 2 conductors with same cross section, stranded max. 1.5 mm²
- Permissible humidity (storage/transport) 30 % ... 70 %
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.0 27141100
- ETIM 4.0 EC000897
- UNSPSC 11 39121410
- UNSPSC 20.0 39121410
- 2 conductors with same cross section, solid min. 0.2 mm²
- Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum 0.25 mm²
- ECLASS 5.1 27141100
- ECLASS 6.0 27141100
- ECLASS 9.0 27141120
- Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
- ECLASS 4.1 27141100
- ETIM 3.0 EC000897
- ETIM 6.0 EC000897
- UNSPSC 18.0 39121410
- Number of levels 2
- Insulating material PA
- Maximum power dissipation for nominal condition 1.02 W (the value is multiplied when connecting multiple levels)
- Nominal current IN 32 A (with 4 mm² conductor cross section)
- Surge voltage test setpoint 7.2 kV
- Tight fit on carrier NS 32/NS 35
- Nominal cross section 4 mm²
- Overvoltage category III
- Potentials 1
- Degree of pollution 3
- Maximum load current 32 A (in case of a 4 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors.)
- Back of the hand protection guaranteed
- Color gray
- Insulating material group I
- Open side panel Yes
- Result of surge voltage test Test passed
- UNSPSC 13.2 39121410
- UNSPSC 19.0 39121410
- Width 6.2 mm
- Nominal voltage UN 500 V (With tightened clamping screws)
- Finger protection guaranteed
- Bending test rotation speed 10 (+/- 2) rpm
- Result of tight fit on support Test passed
- Result of voltage-drop test Test passed
- Acceleration 30g
- Static insulating material application in cold -60 °C
- Smoke gas toxicity NFPA 130 (SMP 800C) passed
- End cover width 2 mm
- Height NS 35/7,5 47 mm
- Length 50.5 mm
- Conductor cross section solid max. 4 mm²
- Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2018-05
- Shock form Half-sine
- Conductor cross section AWG min. 24
- Conductor cross section flexible max. 4 mm²
- Internal cylindrical gage A4
- Result of flexion and pull-out test Test passed
- Power frequency withstand voltage setpoint 1.89 kV
- Setpoint 1 N
- Proof of thermal characteristics (needle flame) effective duration 30 s
- Conductor cross section short circuit testing 4000000 mm²
- Test frequency f1 = 5 Hz to f2 = 250 Hz
- ASD level 6.12 (m/s2)2/Hz
- Number of shocks per direction 3
- Surface flammability NFPA 130 (ASTM E 162) passed
- Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
- Number of connections 3
- Flammability rating according to UL 94 V2
- Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
- Conductor cross section tensile test 4 mm²
- Bending test turns 135
- Requirement temperature-rise test Increase in temperature ≤ 45 K
- Requirements, voltage drop U1 ≤ 3,2 mVU2 ≤ 1,5 x U1dT ≤ 45 K
- Test spectrum Service life test category 2, bogie-mounted
- Test duration per axis 5 h
- Relative insulation material temperature index (Elec., UL 746 B) 130 °C
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
- Height NS 32 52 mm
- Connection method Screw connection
- Connection in acc. with standard CSA
- Conductor cross section flexible min. 0.2 mm²
- Conductor cross section flexible, with ferrule without plastic sleeve max. 4 mm²
- 2 conductors with same cross section, solid max. 1.5 mm²
- Rated surge voltage 6 kV
- Specific optical density of smoke NFPA 130 (ASTM E 662) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
- Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
- Height 38 mm
- Connection 1 level
- Tightening torque, min 0.6 Nm
- Result of power-frequency withstand voltage test Test passed
- Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
- Bending test conductor cross section/weight 0.2 mm² / 0.2 kg
- Tensile test result Test passed
- Tractive force setpoint 60 N
- Result of temperature-rise test Test passed
- Screw thread M3
- Tightening torque max 0.8 Nm
- Max. AWG conductor cross section, flexible 12
- Cross section with insertion bridge, solid max. 4 mm²
- 2 conductors with same cross section, stranded min. 0.2 mm²
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
- Height NS 35/15 54.5 mm
- Stripping length 8 mm
- Conductor cross section AWG max. 12
- Conductor cross section flexible, with ferrule without plastic sleeve min. 0.25 mm²
- Min. AWG conductor cross section, flexible 24
- Conductor cross section flexible, with ferrule with plastic sleeve max. 2.5 mm²
- UNSPSC 6.01 30211811
- Conductor cross section flexible, with ferrule with plastic sleeve min. 0.25 mm²
- Cross section with insertion bridge, stranded max. 4 mm²
- Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 125°C)
- Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum 1.5 mm²
- ECLASS 11.0 27141120
- Ambient temperature (assembly) -5 °C ... 70 °C
- REACh SVHC Lead 7439-92-1
- ECLASS 10.0.1 27141120
- ECLASS 7.0 27141120
- ETIM 2.0 EC000897
- ETIM 7.0 EC000897
- UNSPSC 7.0901 39121410
- UNSPSC 21.0 39121410
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$7.14
Stock:
2,743
Select Qty:
$7.14
$7.14 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨