1111634 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 1111634 TRIO POWER primary-switched power supply in IP67 die-cast housing, input: 1-phase, output: 24 V DC / 10 A
Phoenix Contact

Part#:1111634

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: TRIO POWER primary-switched power supply in IP67 die-cast housing, input: 1-phase, output: 24 V DC / 10 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 1111634 Phoenix Contact price in the box on the right side or send a quick quote.

1111634 Product Details

  • Height
    240 mm
  • Ambient temperature (operation)
    -25 °C ... 70 °C (Derating >60°C: 2.5 %/K)
  • Max. permissible relative humidity (operation)
    ≤ 100 % (at 25 °C, non-condensing)
  • Permissible humidity (operation)
    ≤ 100 % (at 25 °C, non-condensing)
  • Discharge current to PE
    < 3.5 mA
  • Inrush current
    ≤ 25 A (typical)
  • Mains buffering time
    > 15 ms (120 V AC)
  • Nominal output voltage
    24 V DC ±1 %
  • Connection in series
    No
  • Residual ripple
    ≤ 10 mVPP
  • Power loss nominal load max.
    < 22 W (120 V AC)
  • Insulation voltage input/output
    3 kV AC (type test)
  • Type of locking
    M12 screw locking
  • Standard designation
    Degrees of protection provided by enclosures (IP code)
  • Conducted noise emission
    EN 55016
  • Electromagnetic HF field
    EN 61000-4-3
  • Fast transients (burst)
    EN 61000-4-4
  • Voltage dips
    EN 61000-4-11
  • Voltage dip
    0 %
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Degree of pollution
    3
  • Input voltage range
    100 V AC ... 240 V AC 10 %
  • Nominal power consumption
    285 VA
  • Type of protection
    Transient surge protection
  • Dynamic Boost (IDyn.Boost)
    15 A (5 s)
  • Feedback voltage resistance
    ≤ 35 V DC
  • Maximum power dissipation in no-load condition
    < 10 W (120 V AC)
  • Assembly instructions
    Alignable: 20 mm horizontally, 50 mm vertically above, 100 mm vertically below
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Comments
    Criterion A
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Frequency
    50 Hz
  • REACh SVHC
    Lead 7439-92-1
  • Width
    136 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Dielectric strength maximum
    ≤ 300 V AC 15 s
  • Current consumption
    2.8 A (100 V AC)
  • Power factor (cos phi)
    0.93
  • Connection in parallel
    no
  • Output power
    240 W
  • MTBF (IEC 61709, SN 29500)
    > 1800000 h (25 °C)
  • Connection method
    M12 circular connector
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Contact discharge
    6 kV (Test Level 3)
  • Electrostatic discharge
    EN 61000-4-2
  • Signal
    1 kV (Test Level 2 - asymmetrical)
  • Conducted interference
    EN 61000-4-6
  • Criterion A
    Normal operating behavior within the specified limits.
  • Degree of protection
    IP67
  • Installation height
    ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
  • Nominal input voltage range
    100 V AC ... 240 V AC
  • Frequency range (fN)
    50 Hz ... 60 Hz ±10 %
  • Protective circuit/component
    Varistor
  • Nominal output current (IN)
    10 A
  • Control deviation
    < 1 % (change in load, static 10 % ... 90 %)
  • Net weight
    1.5 kg
  • Range of positions
    4 Socket
  • Noise emission
    EN 55016
  • Test field strength
    10 V/m (Test Level 3)
  • Surge voltage load (surge)
    EN 61000-4-5
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • Depth
    53 mm
  • Ambient temperature (start-up type tested)
    -25 °C
  • Climatic class
    3K3 (in acc. with EN 60721)
  • AC frequency range
    50 Hz ... 60 Hz ±10 %
  • Recommended breaker for input protection
    6 A ... 16 A (US/CAN: branch circuit protection < 20 A) (Characteristic B, C, D, K or comparable)
  • Input fuse
    6.3 A (internal (device protection))
  • Derating
    > 60 °C ... 70 °C (2.5%/K)
  • Protection against overvoltage at the output (OVP)
    ≤ 30 V DC
  • Efficiency
    typ. 91 % (120 V AC)
  • Protection class
    I
  • Coding
    L-coded
  • Standards/regulations
    EN/IEC 60529
  • Harmonic currents
    EN 61000-3-2
  • Frequency range
    0.15 MHz ... 80 MHz
  • Input
    2 kV (Test Level 4 - symmetrical)
  • Voltage
    230 V AC
  • Number of periods
    1 period
  • ECLASS 9.0
    27040701

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

1111634

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo