1058044 Phoenix Contact Electrical Measuring & Monitoring Instruments
Part#:1058044
Manufacturer:Phoenix Contact
Product Lifecycle:Active
Checking verified in-stock parts...
About the product: Set consisting of one 1 A measuring transducer and one UV-resistant Rogowski coil with signal line. Length of Rogowski coil: 600 mm, diameter: 140 mm. Length of signal line: 3 m. The Rogowski coil measures the AC current of busbars and power lines.
About the manufacturer: Phoenix Contact develops and manufactures industrial electrical and electronic technology products that power, protect, connect and automate systems and equipment.
Check out the 1058044 Phoenix Contact price in the box on the right side or send a quick quote.
1058044 Product Details
- Maximum altitude < 2000 m
- Position error < 1 %
- Height 85 mm
- Ambient temperature (storage/transport) -40 °C ... 80 °C (Measuring coil)
- Frequency measuring range 40 Hz ... 20000 Hz
- Max. distances for copper cables at PN max 32 m (0.75 mm² (AWG 20))
- Output voltage (sinusoidal, in no-load operation) 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))
- Length of signal cable 3000 mm
- Measuring coil degree of protection IP67 (not assessed by UL)
- Input signal (at 50 Hz) 100 mV (1000 A)
- Ambient temperature (operation) -30 °C ... 80 °C (Measuring coil)
- Nominal supply voltage 24 V DC -20 % ... +25 %
- Linearity error < 0.5 % (From the range end value)
- Rated power 1.5 VA
- Output voltage (in no-load operation) VOUT = M * dI/dt
- Load 0 Ω ... 1.5 Ω
- Housing material Polyamide
- Max. detectable harmonics < 2 kHz
- Operating voltage display Green LED
- Stripping length 7 mm
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Torque 0.5 Nm ... 0.6 Nm
- ECLASS 5.1 27210900
- ETIM 7.0 EC002048
- Depth 70.4 mm
- Diameter of measuring coil 8.3 mm ±0.2 mm
- Current output signal 0 A AC ... 1 A
- Coil material Elastollan
- Maximum transmission error ≤ 0.5 % (From the range end value)
- Temperature coefficients 0.005 %/K (+10 °C ... +70 °C, both components have the same ambient temperature)
- Screw thread M3
- Overvoltage category III (1000 V, to neutral conductor)
- ECLASS 11.0 27210902
- ETIM 6.0 EC002048
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Nominal supply voltage range 19.2 V DC ... 30 V DC
- Power consumption 4 W
- Input impedance 27 kΩ (smallest measuring range)
- Phase angle < 1 °
- Length of measuring coil 450 mm
- Rated insulation voltage 1000 V AC (rms CAT III)
- Frequency range 45 Hz ... 65 Hz
- UL, USA/Canada UL 508 Listed
- Connection name Measuring transducer side
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- REACh SVHC Lead 7439-92-1
- ECLASS 4.0 27210900
- ECLASS 7.0 27210902
- Width 22.5 mm
- Measuring transducer degree of protection IP20
- Max. current consumption 190 mA
- Measuring ranges (current) 100 A 250 A 400 A 630 A 1000 A 1500 A 2000 A 4000 A
- Configurable/programmable Via DIP switches
- Output signal (at 50 Hz) 100 mV (no load, at 1,000 A)
- Conductor structure signal line 2x 0.22 mm (Signal (tinned))
- Test voltage 1.5 kV AC (Supply/input and output: 50 Hz, 1 min)
- Current consumption < 190 mA (at 19.2 V)
- Typical measuring error < 1 %
- Conductor cross section AWG 24 ... 14
- ECLASS 10.0.1 27210902
- ECLASS 6.0 27210900
- ECLASS 9.0 27210902
- Insulation double insulation
- Basic accuracy <± 0.21 %
- Standards/regulations IEC 61010-1
- Connection method Screw connection
- Pollution degree 2
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.1 27210900
- ECLASS 5.0 27210900
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
Shipping and Delivery Worldwide
calculate cost and time at Checkout
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨