About the product: Ex i temperature transducer: converts signals from resistance temperature detectors installed in the Ex area and transmits a 0/4 - 20 mA signal to a load in the safe area. Freely programmable. 3-way isolation, SIL, screw connection, standard configuration
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 1050222 Phoenix Contact price in the box on the right side or send a quick quote.
1050222 Product Details
- ECLASS 7.0 27210120
- Screw thread M3
- Height 112.5 mm
- Degree of protection IP20
- Rated insulation voltage 300 Vrms
- Input signal range 0 Ω ... 50 kΩ
- Measuring range span ≥ 50 K
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Status display Green LED (supply voltage, PWR)
- Color gray
- Degree of pollution 2
- Max. external capacitance Co 2 µF
- Standards/regulations GB 3626.20
- DNV GL-Humidity B
- Additional text and EN 61326
- Nominal supply voltage 24 V DC
- Behavior in the event of a sensor error As per NE 43 or can be freely defined
- Power consumption ≤ 1 W
- Conductor cross section AWG 24 ... 14
- Ambient temperature (operation) 49 °C
- Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
- Temperature measuring range -200 °C ... 850 °C (Range depending on the sensor type)
- Potentiometer resistance range 0 Ω ... 50 kΩ
- Configurable/programmable Yes
- Alignment zero ± 5 %
- Insulation Safe isolation in accordance with IEC/EN 61010-1
- Max. output voltage Uo 3.5 V
- Max. output power Po 350 mW
- Input current Ii 100 mA
- Conformance CE-compliant, additionally EN 61326
- DNV GL-Temperature B
- Temperature B
- Vibration A
- REACh SVHC Lead 7439-92-1
- ECLASS 4.0 27210120
- Depth 114.5 mm
- Test voltage 2.5 kV AC (50 Hz, 1 min.)
- Sensor types (RTD) that can be used Sensors (2-, 3-, 4-conductor)
- Signal output Current output
- Output ripple (current) < 15 µAPP
- Stripping length 7 mm
- No. of channels 1
- Temperature coefficient, typical 0.01 %/K
- Interference emission EN 61000-6-4
- Overvoltage category II
- Max. output current Io 400 mA
- Input voltage Ui 7 V
- Noise emission EN 61000-6-4
- IECEx [Ex ia Ma] I
- DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
- Humidity B
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 11.0 27210129
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Ambient temperature (storage/transport) -40 °C ... 80 °C
- Altitude ≤ 5000 m
- Max. permissible overall conductor resistance 50 Ω (Per cable)
- Current output signal 0 mA ... 20 mA
- Supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
- Connection method Screw connection
- Torque 0.5 Nm ... 0.6 Nm
- Step response (0–99%) typ. 1 s
- Housing material PA 6.6-FR
- Designation EAC Ex
- Max. internal capacitance Ci 47 µF
- Max. external inductivity Lo 20 µH
- Input power Pi 550 mW
- Typical deviation from the measuring range final value 1 %
- DNV GL-EMC B
- Identification [Ex ia Ga] IIC
- Enclosure Required protection according to the Rules shall be provided upon installation on board
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Input Intrinsically safe
- Sensor input current 10 µA ... 210 µA (Up to 2x 210 µA with 3-conductor technology)
- Load/output load current output ≤ 600 Ω
- Power dissipation ≤ 0.76 W
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Transmission error, typical 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA)
- Alignment span ± 5 %
- Electromagnetic compatibility Conformance with EMC directive
- Electrical isolation 375 V (Peak value in accordance with IEC/EN 60079-11)
- Group IIC/IIB/IIA
- Safety-related maximum voltage Um 253 V AC (125 V DC, Zone 2: 3.1, 3.2 = 30 V DC)
- ATEX I (M1) [Ex ia Ma] I
- DNV GL-Vibration A
- Certificate RU C-DE.AB72.B.00093/19
- EMC B
- Width 12.5 mm
- ETIM 3.0 EC001446
- ETIM 6.0 EC002919
- UNSPSC 7.0901 39121008
- UNSPSC 13.2 41112105
- UNSPSC 20.0 41112105
- ECLASS 5.1 27210120
- ETIM 4.0 EC001446
- UNSPSC 11 39121008
- ECLASS 10.0.1 27210129
- ECLASS 9.0 27210129
- UNSPSC 12.01 39121008
- UNSPSC 19.0 41112105
- ECLASS 4.1 27210120
- ECLASS 6.0 27210120
- UNSPSC 18.0 41112105
- UNSPSC 6.01 30211506
- ECLASS 5.0 27210120
- ETIM 2.0 EC001446
- ETIM 7.0 EC002919
- UNSPSC 21.0 41112105
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
1050222
Select Qty:
Average response time: 11 minutes
Shipping and Delivery Worldwide