Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

1046805 Phoenix Contact DC/DC Converters

Phoenix Contact 1046805 Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, SFB Technology (Selective Fuse Breaking), Screw connection, input: 24 V DC , output: 24 V DC / 20 A
Phoenix Contact

Part#:1046805

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, SFB Technology (Selective Fuse Breaking), Screw connection, input: 24 V DC , output: 24 V DC / 20 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers DC/DC Converters that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 1046805 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Weight1.2 kg
  • Typical current consumption
    27 A (24 V DC)
  • Input voltage range
    18 V DC ... 32 V DC
  • Switch-on time
    < 1 s
  • Typical response time
    300 ms (from SLEEP MODE)
  • Type test (IEC/EN 60950-1) B
    4 kV DC
  • Selective Fuse Breaking (ISFB)
    120 A (15 ms)
  • Feedback voltage resistance
    ≤ 35 V DC
  • POut
    > 100 % (LED lights up yellow, output power > 480 W)
  • Voltage
    1 kV
  • Side element version
    Aluminum
  • Height with alternative assembly
    130 mm
  • Depth with alternative assembly
    73 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Climatic class
    3K3 (EN 60721)
  • EMC requirements, power plant
    IEC 61850-3
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Discharge in air
    15 kV (Test Level 4)
  • Comments
    Criterion A
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Surge voltage load (surge)
    EN 61000-4-5
  • Voltage dips
    EN 61000-4-29
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Test level 4
    15 kHz 150 kHz (Test Level 3)
  • Input, output (test level 3)
    10 MHz (Test Level 2 - asymmetrical)
  • Inrush current limitation typical
    2.7 A (after 1 ms)
  • Type test (IEC/EN 60950-1) C
    0.5 kV DC
  • Production test C
    0.5 kV DC
  • Stripping length
    8 mm
  • Flexible conductor cross section (ferrule with plastic sleeve)
    0.2 mm² ... 0.75 mm²
  • Static Boost (IStat.Boost)
    25 A
  • System deviation, static
    < 3 % (change in load, static 10 % ... 90 %)
  • Residual ripple
    < 50 mVPP
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • UOut
    > 0.9 x USet (LED lights up green)
  • Time
    278680 h
  • Protection class
    Special with SELV input and output
  • Width
    70 mm
  • Depth
    125 mm
  • Power loss nominal load max.
    < 26.6 W
  • Mains buffering
    typ. 16 ms (24 V DC)
  • Type test (IEC/EN 60950-1) A
    2 kV DC
  • Production test B
    2 kV DC
  • Conductor cross section flexible
    0.2 mm² ... 1.5 mm²
  • Conductor cross section AWG
    24 ... 16
  • Torque
    0.6 Nm ... 0.8 Nm
  • System deviation, dynamic
    < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
  • Short-circuit-proof
    yes
  • Rise time
    < 1 s (UOUT (10 % ... 90 %))
  • UIn
    > 0.8 x UInNom (LED off)
  • Temperature
    30 °C
  • Electric strength, max.
    35 V DC (60 s)
  • Inrush current integral (I2t)
    < 0.2 A2s
  • Production test A
    2 kV DC
  • Connection method
    Push-in connection
  • Conductor cross section solid
    0.2 mm² ... 1 mm²
  • Nominal output current (IN)
    20 A
  • Setting range of the output voltage (USet)
    24 V DC ... 29.5 V DC (> 24 V DC, constant capacity)
  • System deviation, input voltage change
    < 0.4 % (change in input voltage ±10 %)
  • Connection in series
    yes
  • MTBF (IEC 61709, SN 29500)
    > 1034000 h (25 °C)
  • Auxiliary converter stage
    190 kHz ... 220 kHz (Auxiliary converter stage)
  • Degree of protection
    IP20
  • Height
    130 mm
  • Efficiency
    typ. 94.7 % (24 V DC)
  • Maximum power dissipation in no-load condition
    < 4 W
  • Power dissipation SLEEP MODE
    < 2 W
  • Overvoltage category EN 61010-1
    II
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Additional text
    Test Level 2
  • Electrostatic discharge
    EN 61000-4-2
  • Frequency range
    50 Hz ... 60 Hz
  • Test field strength
    100 A/m
  • Conducted interference
    EN 61000-4-6
  • Damped oscillating magnetic field
    EN 61000-4-10
  • Test level 1
    15 Hz 150 Hz (Test Level 3)
  • Alternating component of DC voltage
    EN 61000-4-17
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • ECLASS 9.0
    27210901
  • Insulation voltage input/output
    4 kV DC (type test)
  • Type test (IEC/EN 60950-1) D
    0.5 kV DC
  • Production test D
    0.5 kV DC
  • Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)
    0.2 mm² ... 1.5 mm²
  • Nominal output voltage (UN)
    24 V DC
  • Dynamic Boost (IDyn.Boost)
    30 A (5 s)
  • Magnetic circuit breaker tripping
    A1...A16 / B2...B13 / C1...C6 / Z1...Z16
  • No-load proof
    yes
  • Types of signaling
    LED
  • Protection against overvoltage at the output (OVP)
    ≤ 32 V DC
  • Output current
    20 A
  • Main converter stage
    67 kHz ... 135 kHz (Main converter stage)
  • Hood version
    Stainless steel X6Cr17
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Vibration (operation)
    5 Hz ... 100 Hz resonance search 2.3g, 90 min, resonance frequency 2.3g, 90 min
  • Overvoltage category EN 62477-1
    III
  • Conducted noise emission
    EN 55016
  • Contact discharge
    8 kV (Test Level 4)
  • Input
    1 kV (Test Level 3 - symmetrical)
  • I/O/S
    asymmetrical
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Attenuated oscillating wave
    EN 61000-4-18
  • Input, output (test level 2)
    100 kHz 1 MHz (Test Level 2 - asymmetrical)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • ECLASS 11.0
    27210901
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Width with alternative assembly
    122 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Degree of pollution
    2
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Standards/regulations
    EN 61000-4-29
  • Noise emission
    EN 55016
  • Fast transients (burst)
    EN 61000-4-4
  • Signal
    2 kV (Test Level 3 - asymmetrical)
  • Frequency
    0 Hz
  • Test level 2
    150 Hz 1.5 kHz (Test Level 3)
  • Test level 3
    1.5 kHz 15 kHz (Test Level 3)
  • Test level 5
    16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
  • Signals (test level 1)
    100 kHz 1 MHz (Test Level 2 - symmetrical)
  • Maximum altitude
    ≤ 5000 m (> 2000 m, observe derating)
  • Shock
    18 ms, 30g, in each space direction (according to IEC 60068-2-27)
  • Standard designation
    Mains variation/undervoltage
  • DNV GL conducted interference
    Class B
  • DNV GL noise radiation
    Class B
  • Electromagnetic HF field
    EN 61000-4-3
  • Power frequency magnetic field
    EN 61000-4-8
  • Voltage dip
    0 %
  • Test level 6
    0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
  • Input, output (test level 1)
    100 kHz 1 MHz (Test Level 2 - symmetrical)
  • Signals (test level 2)
    100 kHz 1 MHz (Test Level 2 - asymmetrical)
  • ECLASS 10.0.1
    27210901
  • Criterion A
    Normal operating behavior within the specified limits.

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo