2904621 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2904621 Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 3-phase, output: 24 V DC/10 A
Phoenix Contact

Part#:2904621

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 6

Apr 25, 2024

About the product: Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 3-phase, output: 24 V DC/10 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2904621 Phoenix Contact price in the box on the right side or send a quick quote.

2904621 Product Details

  • Width with alternative assembly
    122 mm
  • Installation distance right/left
    5 mm / 5 mm
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Degree of pollution
    2
  • Input voltage range
    3x 400 V AC ... 500 V AC -20 % ... +10 %
  • Current consumption
    3x 0.5 A (400 V AC)
  • Mains buffering time
    typ. 29 ms (3x 400 V AC)
  • Nominal output voltage
    24 V DC
  • Derating
    > 60 °C ... 70 °C (2.5%/K)
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Residual ripple
    < 75 mVPP (with nominal values)
  • Power loss nominal load max.
    < 19 W (400 V AC)
  • MTBF (IEC 61709, SN 29500)
    > 1034000 h (25 °C)
  • Connection method
    Push-in connection
  • Conductor cross section flexible min.
    0.2 mm²
  • Conductor cross section AWG max.
    16
  • Standard - Electrical safety
    IEC 61010-2-201 (SELV)
  • Width
    50 mm
  • Depth with alternative assembly
    53 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Nominal input voltage range
    3x 400 V AC ... 500 V AC
  • Frequency range (fN)
    50 Hz ... 60 Hz -10 % ... +10 %
  • Power factor (cos phi)
    0.91
  • Protective circuit/component
    Varistor, gas-filled surge arrester
  • Nominal output current (IN)
    10 A
  • Feedback voltage resistance
    ≤ 35 V DC
  • Control deviation
    < 0.5 % (Static load change 10 % ... 90 %)
  • Efficiency
    typ. 93 % (400 V AC)
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section AWG min.
    24
  • Standard - Safety of transformers
    IEC 61558-2-16 pending
  • Standard - Safe isolation
    IEC 61558-2-16 pending
  • CSA
    CAN/CSA-C22.2 No. 60950-1-07
  • SIQ
    BG (type approved)
  • Conducted noise emission
    EN 55016
  • DNV GL noise radiation
    Class B
  • Discharge in air
    15 kV (Test Level 4)
  • Electromagnetic HF field
    EN 61000-4-3
  • Signal
    4 kV (Test Level 4 - asymmetrical)
  • Voltage dips
    EN 61000-4-11
  • Height
    130 mm
  • Installation distance top/bottom
    50 mm / 50 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Inrush current
    typ. 3 A (at 25 °C)
  • Recommended breaker for input protection
    3x 4 A ... 20 A (Characteristic B, C or comparable)
  • Selective Fuse Breaking (ISFB)
    60 A (15 ms)
  • Output power
    240 W
  • Net weight
    0.9 kg
  • Environmental protection directive
    RoHS Directive 2011/65/EU
  • Insulation voltage input / PE
    3.5 kV AC (type test)
  • Conductor cross section flexible max.
    1.5 mm²
  • Stripping length
    8 mm
  • EMC requirements, power plant
    IEC 61850-3
  • Standard - power supply devices for low voltage with DC output
    EN 61204-3
  • Rail applications
    EN 50121-3-2
  • Noise emission
    EN 55016
  • DNV GL conducted interference
    Class A
  • Test field strength
    110 A/m
  • Comments
    Criterion A
  • Conducted interference
    EN 61000-4-6
  • I/O/S
    asymmetrical
  • Number of periods
    5 / 10 / 50 periods
  • Test level 1
    15 Hz 150 Hz (Test Level 4)
  • Test level 3
    1.5 kHz 15 kHz (Test Level 4)
  • Input, output (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Depth
    125 mm
  • Degree of protection
    IP20
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Discharge current to PE
    < 3.5 mA
  • Nominal power consumption
    274 VA
  • Static Boost (IStat.Boost)
    12.5 A
  • Connection in series
    yes
  • Typical response time
    300 ms (from SLEEP MODE)
  • Insulation voltage input/output
    4 kV AC (type test)
  • Protection class
    I
  • Assembly instructions
    alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Standard – Safety extra-low voltage
    IEC 61010-1 (SELV)
  • Standard - safety for equipment for measurement, control, and laboratory use
    IEC 61010-1
  • UL approvals
    UL Listed UL 508
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Flicker
    EN 61000-3-3
  • Electrostatic discharge
    EN 61000-4-2
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Frequency
    50 Hz
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Attenuated oscillating wave
    EN 61000-4-18
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • ECLASS 5.1
    27242213
  • UNSPSC 21.0
    39121004
  • Height with alternative assembly
    130 mm
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Installation height
    ≤ 5000 m (> 2000 m, observe derating)
  • AC frequency range
    50 Hz ... 60 Hz -10 % ... +10 %
  • Type of protection
    Transient surge protection
  • Setting range of the output voltage (USet)
    24 V DC ... 29.5 V DC (constant capacity)
  • Dynamic Boost (IDyn.Boost)
    20 A (5 s)
  • Protection against overvoltage at the output (OVP)
    ≤ 32 V DC
  • Maximum power dissipation in no-load condition
    < 5 W (400 V AC)
  • Insulation voltage output / PE
    0.5 kV DC (type test)
  • Conductor cross section solid max.
    1 mm²
  • EMC requirements for noise emission
    EN 61000-6-3
  • HART FSK Physical Layer Test Specification Compliance
    Output voltage UOut compliant
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • Shipbuilding approval
    DNV GL, PRS, BV, LR, ABS
  • Additional text
    Test Level 2
  • Frequency range
    50 Hz ... 60 Hz
  • Fast transients (burst)
    EN 61000-4-4
  • Power frequency magnetic field
    EN 61000-4-8
  • Voltage dip
    40 %
  • Test level 2
    150 Hz 1.5 kHz (Test Level 4)
  • Test level 4
    15 kHz 150 kHz (Test Level 4)
  • Test level 6
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Input, output (test level 3)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • ECLASS 6.0
    27049005
  • ECLASS 9.0
    27040701
  • Mains variation/undervoltage
    SEMI F47-0706, EN 61000-4-11
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Harmonic currents
    EN 61000-3-2
  • Contact discharge
    8 kV (Test Level 4)
  • Input
    2 kV (Test Level 4 - symmetrical)
  • Surge voltage load (surge)
    EN 61000-4-5
  • Voltage
    2.5 kV
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Attenuated sinusoidal oscillations (ring wave)
    EN 61000-4-12
  • Test level 5
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Signals (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Criterion A
    Normal operating behavior within the specified limits.
  • ECLASS 11.0
    27040701
  • ETIM 6.0
    EC002540
  • UNSPSC 20.0
    39121004
  • Damped oscillating magnetic field
    EN 61000-4-10
  • Input, output (test level 2)
    10 MHz
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • UNSPSC 18.0
    39121004
  • Signals (test level 2)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 10.0.1
    27040701
  • UNSPSC 13.2
    39121004
  • UNSPSC 19.0
    39121004

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 3 days!

1-year warranty

$287.94

2904621

Stock:

6

Select Qty:

$287.94

$287.94 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo