About the product: Monitoring relay for monitoring 3-phase voltages of 350…650 V AC, undervoltage, window, phase sequence, phase failure, asymmetry, supply voltage can be selected via power module, 2 changeover contacts
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Relays that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2867979 Phoenix Contact price in the box on the right side or send a quick quote.
2867979 Product Details
- Ambient temperature (operation) -25 °C ... 55 °C
- Width 45 mm
- Interrupting rating (ohmic load) max. 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
- Mechanical service life approx. 2x 107 cycles
- Housing insulation material Polyamide PA, self-extinguishing
- Conductor cross section AWG 20 ... 14
- Stripping length 8 mm
- Low Voltage Directive Conformance with LV directive 2006/95/EC
- Depth 113 mm
- Degree of protection IP40 (Housing)
- Min. setting range -30 % ... 20 % (From UN)
- Insulation Basic insulation
- ECLASS 4.0 27371100
- Basic accuracy ± 5 % (of scale end value)
- Asymmetry 5 % ... 25% / OFF
- ECLASS 7.0 27371801
- Height 90 mm
- Permissible humidity (operation) 15 % ... 85 %
- Noise immunity EN 61000-6-2
- Setting range for response delay 0.1 s ... 10 s
- Min setting range of the voltage threshold value 350 V AC ... 600 V AC
- Maximum switching voltage 250 V AC (in acc. with IEC 60664-1)
- Contact type 2 floating changeover contacts
- Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
- Color green
- Noise emission EN 61000-6-3
- Overvoltage category III
- ECLASS 4.1 27371100
- ETIM 2.0 EC001438
- Ambient temperature (storage/transport) -25 °C ... 70 °C
- Function Undervoltage, window, asymmetry, phase sequence, phase failure
- Nominal input voltage UN 3 ~ 500 V
- Setting accuracy ≤ 5 % (of scale end value)
- Output fuse 5 A (fast-blow)
- Operating mode 100% operating factor
- Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
- Conductor cross section solid 0.5 mm² ... 2.5 mm²
- Conductor cross section flexible 0.25 mm² ... 2.5 mm²
- Rated insulation voltage 600 V
- China RoHS Environmentally friendly use period: unlimited = EFUP-e
- ECLASS 11.0 27371801
- Maximum temperature coefficient < 0.1 %/K
- Max. setting range -20 % ... 30 % (From UN)
- Max. setting range of the voltage threshold value 400 V AC ... 650 V AC
- Repeat accuracy ≤ 2 %
- Recovery time 500 ms
- Mounting position any
- Supply voltage range 230 V AC ... 500 V AC (see Power modules)
- Connection method Screw connection
- Tightening torque 1 Nm
- Standards/regulations EN 50178
- Pollution degree 2
- ECLASS 5.0 27371800
- ECLASS 5.1 27371800
- ETIM 3.0 EC001438
- UNSPSC 7.0901 39121535
- UNSPSC 11 39121535
- ETIM 7.0 EC001438
- UNSPSC 13.2 41113620
- UNSPSC 19.0 41113620
- ECLASS 6.0 27371800
- ETIM 4.0 EC001438
- ETIM 6.0 EC001438
- ECLASS 10.0.1 27371801
- ECLASS 9.0 27371801
- UNSPSC 21.0 41113620
- UNSPSC 18.0 41113620
- UNSPSC 6.01 30211916
- UNSPSC 12.01 39121535
- UNSPSC 20.0 41113620
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
2867979
Select Qty:
Average response time: 11 minutes
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨