About the product: Current measuring transducer for 5 A and 12 A AC, the output signal 0...20 mA or 4...20 mA, can be configured using a DIP switch with an operating mode indication through an LED
About the manufacturer: Phoenix Contact develops and manufactures industrial electrical and electronic technology products that power, protect, connect and automate systems and equipment.
Check out the 2810638 Phoenix Contact price in the box on the right side or send a quick quote.
2810638 Product Details
- Width 22.5 mm
- Ambient temperature (storage/transport) -40 °C ... 85 °C (-40 °F ... 185 °F)
- Degree of protection IP20
- Setting range for max. input current 0 A AC ... 12 A (configurable)
- Nominal frequency fN 50 Hz
- Max. output current 25 mA
- Load/output load current output < 500 Ω (20 mA)
- Screw thread M3
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Maximum temperature coefficient < 0.02 %/K
- Mounting position any
- Housing material Polyamide PA non-reinforced
- Height 104 mm
- Depth 114.5 mm
- ECLASS 11.0 27210123
- ECLASS 4.1 27200300
- ETIM 6.0 EC002475
- UNSPSC 18.0 39121032
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Configurable/programmable Via DIP switches
- Overload capacity 1 x IN (continuous)
- Connection method Screw connection
- Current output signal 0 mA ... 20 mA (configurable)
- Max. current consumption < 33 mA (at 24 V DC)
- Status display LED red (error), LED green (ready)
- Maximum transmission error ≤ 0.5 % (of nominal range value under nominal conditions)
- Rated insulation voltage 300 V AC (to earth)
- Test voltage output/power supply 2 kV (50 Hz, 1 min.)
- Color gray
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 6.0 27210100
- ECLASS 7.0 27210123
- UNSPSC 6.01 30211501
- UNSPSC 11 39121006
- Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
- Input current range 0 A ... 12 A
- Surge strength 8 x IN (1 s)
- Output name No switching output
- Supply voltage range 19.2 V AC/DC ... 253 V AC/DC
- Stripping length 8 mm
- Conductor cross section AWG 24 ... 14
- Degree of pollution 2
- Test voltage input/output 4 kV (50 Hz, 1 min.)
- Electromagnetic compatibility Conformance with EMC directive
- ATEX II 3 G Ex nA IIC T4 Gc X
- ECLASS 4.0 27271100
- ECLASS 10.0.1 27210123
- ECLASS 5.1 27200300
- ETIM 7.0 EC002475
- UNSPSC 20.0 39121032
- Ambient temperature (operation) -20 °C ... 65 °C (-4 °F ... 149 °F)
- Setting range for min. input current 0 A AC ... 5 A (configurable)
- Frequency measuring range 45 Hz ... 65 Hz
- Ripple < 10 mVPP (for 500 Ω at 20 mA)
- Power consumption < 0.8 W (at 24 V DC)
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Step response (10-90%) < 300 ms
- Temperature coefficient, typical < 0.015 %/K
- Noise emission EN 61000-6-4
- Conformance CE-compliant
- Designation ATEX
- ECLASS 5.0 27200300
- ECLASS 9.0 27210123
- UNSPSC 7.0901 39121019
- UNSPSC 12.01 39121006
- UNSPSC 21.0 39121032
- Identification II 3 G Ex nA IIC T4 Gc X
- REACh SVHC N,N-dimethylacetamide 127-19-5
- ETIM 3.0 EC002475
- ETIM 4.0 EC002475
- UNSPSC 19.0 39121032
- UNSPSC 13.2 39121032
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
Shipping and Delivery Worldwide
calculate cost and time at Checkout
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨