Nikki Gonzales
Nick Goetz
Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

2800983 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2800983 Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module for four signal wires with common reference potential. Indirect grounding via gas-filled surge arrester.
Phoenix Contact

Part#:2800983

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 29

04/17/2024

About the product: Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module for four signal wires with common reference potential. Indirect grounding via gas-filled surge arrester.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2800983 Phoenix Contact price in the box on the right side or send a quick quote.

2800983 Product Details

  • Height
    91.1 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Mounting type
    DIN rail: 35 mm
  • Depth
    77.5 mm (incl. DIN rail 7.5 mm)
  • Color
    jet black RAL 9005
  • Type
    DIN rail module, two-section, divisible
  • Rated current
    700 mA (50 °C)
  • Voltage protection level Up static (line-earth)
    ≤ 80 V (C2 - 10 kV / 5 kA)
  • Total discharge current Itotal (8/20) µs
    20 kA
  • Max. required back-up fuse
    800 mA (FF)
  • Connection method
    DIN rail NS35
  • Standards/specifications
    IEC 61643-21 2000 + A1:2008, modified
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 5.1
    27130800
  • ETIM 3.0
    EC000943
  • UNSPSC 7.0901
    39121610
  • UNSPSC 13.2
    39121620
  • UNSPSC 21.0
    39121620
  • Ambient temperature (operation)
    -40 °C ... 70 °C
  • Altitude
    ≤ 4000 m (amsl (above mean sea level))
  • Nominal voltage UN
    24 V DC
  • Pulse discharge current Iimp (10/350) µs (line-earth)
    2.5 kA
  • Voltage protection level Up (line-earth)
    ≤ 800 V (C1 - 1 kV/500 A)
  • Surge protection fault message
    Optical, multi-stage
  • Pulse reset time (line-signalground)
    ≤ 350 ms
  • Conductor cross section solid
    0.2 mm² ... 4 mm²
  • ECLASS 4.0
    27130800
  • ECLASS 9.0
    27130807
  • UNSPSC 6.01
    30212010
  • UNSPSC 19.0
    39121620
  • Width
    17.7 mm
  • Housing material
    PA 6.6
  • Note
    Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
  • IEC test classification
    C1
  • Voltage protection level Up (line-signalground)
    ≤ 75 V (C1 - 1 kV/500 A)
  • Response time tA (line-earth)
    ≤ 100 ns
  • Cut-off frequency fg (3 dB), asym. (signal ground) in 150 Ω system
    typ. 1.1 MHz
  • Impulse durability (line-earth)
    C1 - 1 kV / 500 A
  • Screw thread
    M3
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • ECLASS 11.0
    27130807
  • ECLASS 5.0
    27130800
  • ECLASS 7.0
    27130807
  • UNSPSC 11
    39121610
  • UNSPSC 12.01
    39121610
  • Horizontal pitch
    1 Div.
  • Degree of protection
    IP20
  • Flammability rating according to UL 94
    V-0
  • Operating effective current IC at UC
    ≤ 1 mA (per path)
  • Nominal discharge current In (8/20) µs (line-earth)
    10 kA
  • Response time tA (line-signalground)
    ≤ 1 ns
  • Input attenuation aE, asym.
    typ. 0.3 dB (≤ 300 kHz / 150 Ω)
  • Resistance per path
    1.2 Ω ±5 %
  • Impulse durability (line-signalground)
    C1 - 1 kV / 500 A
  • Stripping length
    8 mm
  • Conductor cross section AWG
    24 ... 12
  • ECLASS 10.0.1
    27130807
  • ECLASS 4.1
    27130800
  • ETIM 6.0
    EC000943
  • UNSPSC 18.0
    39121620
  • Direction of action
    Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
  • Maximum continuous voltage UC
    30 V DC
  • Residual current IPE
    ≤ 1 µA
  • Capacity (line-earth)
    typ. 2 nF
  • Pulse reset time (line-earth)
    ≤ 30 ms
  • Tightening torque
    0.5 Nm
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 6.0
    27130800
  • ETIM 4.0
    EC000943
  • ETIM 7.0
    EC000943
  • UNSPSC 20.0
    39121620

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 24h!

1-year warranty

$385.00

2800983

Stock:

29

Select Qty:

$385.00

$385.00 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo