2800903 Product Details
- Height 45 mm
- Vibration (operation) 3g (according to IEC 60068-2-6, Test Fc)
- Installation instructions When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).Special precautionary measures must be taken in systems or mac
- Mounting type on base element
- Operating voltage 24 V DC
- Active current limitation typ. 1.25 x IN
- Auxiliary type of contact floating signal contact
- Maximum auxiliary contact operating voltage 30 V DC
- Minimum auxiliary contact operating current 10 mA
- ECLASS 4.0 27141100
- ECLASS 6.0 27141100
- ECLASS 9.0 27141116
- UNSPSC 11 39121411
- UNSPSC 20.0 39121410
- Width 12.3 mm
- Ambient temperature (operation) -25 °C ... 50 °C (non-condensing)
- Flammability rating according to UL 94 V-0
- Degree of pollution 2
- Dielectric strength max. 30 V DC (Load circuit)
- Required backup fuse not required, integrated failsafe element
- Max. capacitive load load circuit 20000 µF
- REACh SVHC Lead 7439-92-1
- ECLASS 5.0 27141100
- ECLASS 7.0 27141116
- ETIM 7.0 EC000899
- UNSPSC 6.01 30211812
- UNSPSC 18.0 39121410
- Complete module height 90 mm
- Complete module depth 77.3 mm
- Ambient temperature (storage/transport) -40 °C ... 70 °C
- Type Male
- Closed circuit current I0 typ. 8 mA (When switched on)
- Power dissipation 0.77 W (Nominal operation)
- Undervoltage switch-off load circuit < 14 V (typ. OFF)
- Maximum auxiliary contact operating current 0.5 A
- Designation Shipbuilding approval
- ECLASS 10.0.1 27140401
- ETIM 3.0 EC000899
- ETIM 4.0 EC000899
- UNSPSC 7.0901 39121411
- UNSPSC 13.2 39121410
- Complete module width 12.3 mm
- Degree of protection IP30 (Actuation area)
- Color gray
- Rated surge voltage 0.5 kV
- Tripping method E (electronic)
- Voltage drop 120 mV (at IN)
- Standards/specifications EMV EN 61000-6-3 Interference emission
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.1 27141100
- Depth 52 mm
- Humidity test 96 h, 95 % RH, 40 °C
- Number of positions 1
- Fuse type electronic
- Nominal current IN 3 A
- Temperature derating 3 A (at 50 °C)
- Shutdown time load circuit 300 ms (see time/current characteristic curve)
- Minimum auxiliary contact operating voltage 10 V DC
- Identification DNV GL
- ECLASS 11.0 27140401
- ECLASS 5.1 27141100
- ETIM 6.0 EC000899
- UNSPSC 12.01 39121411
- UNSPSC 19.0 39121410
- UNSPSC 21.0 39121410
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
Shipping and Delivery Worldwide
calculate cost and time at Checkout
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨