Welcome to Quotebeam
Nikki Gonzales
Bryan Obida
Nick Goetz

Live support:

Monday - Friday 6AM - 6PM PST

2702864 Phoenix Contact Programmable Logic Controllers

Phoenix Contact 2702864 Axioline F, DALI master, two channels, integrated DALI power supply unit, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
Phoenix Contact

Part#:2702864

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Checking verified in-stock parts...

About the product: Axioline F, DALI master, two channels, integrated DALI power supply unit, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

About the manufacturer: Phoenix Contact develops and manufactures industrial electrical and electronic technology products that power, protect, connect and automate systems and equipment.

Check out the 2702864 Phoenix Contact price in the box on the right side or send a quick quote.

2702864 Product Details

  • Number
    2
  • ECLASS 5.1
    27242608
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • Note on dimensions
    The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
  • Air pressure (operation)
    70 kPa ... 106 kPa (up to 3000 m above sea level)
  • Note on weight specifications
    with connectors and bus base module
  • Note
    The data apply for DALI bus 1 and DALI bus 2, respectively.
  • Transmission speed
    100 Mbps
  • Output current with short-circuit
    max. 250 mA
  • Supply voltage range
    19.2 V DC ... 30 V DC (including all tolerances, including ripple)
  • Immunity to burst
    Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
  • Mechanical tests
    Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.0
    27250203
  • Height
    126.1 mm
  • Degree of protection
    IP20
  • Ambient temperature (operation)
    -25 °C ... 60 °C
  • Net weight
    190.5 g
  • Connection method
    Bus base module
  • Current carrying capacity
    max. 195 mA (Bus load)
  • Type of protection
    Bus protected up to 250 V AC, maximum
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • Protection
    max. 8 A (polarity reversal protection up to 5 A)
  • Test section
    5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC 50 Hz 1 min.
  • ECLASS 9.0
    27242608
  • ECLASS 7.0
    27242608
  • UNSPSC 7.0901
    43201404
  • UNSPSC 13.2
    32151602
  • Depth
    54 mm
  • Permissible humidity (storage/transport)
    5 % ... 95 % (non-condensing)
  • Color
    traffic grey A RAL 7042
  • Designation
    Feed-in of supply voltage (UI)
  • Output current
    230 mA (guaranteed)
  • Supply voltage
    24 V DC
  • Protective circuit
    Surge protection electronic (35 V, 0.5 s)
  • Immunity to EF
    Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
  • Interference emission
    Noise emission test according to EN 61000-6-3 Class B
  • ECLASS 5.0
    27250203
  • Width
    35 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Mounting position
    any (no temperature derating)
  • Current consumption
    typ. 250 mA
  • Air pressure (storage/transport)
    70 kPa ... 106 kPa (up to 3000 m above sea level)
  • Mounting type
    DIN rail
  • Power consumption
    max. 8.8 W (Both channels loaded with 195 mA)
  • ECLASS 4.1
    27250203
  • ECLASS 6.0
    27242600
  • ETIM 2.0
    EC001434
  • ETIM 4.0
    EC001601
  • UNSPSC 6.01
    43172015
  • UNSPSC 12.01
    43201404
  • ETIM 7.0
    EC001604
  • ETIM 6.0
    EC001604
  • UNSPSC 11
    43172015
  • UNSPSC 19.0
    32151602
  • UNSPSC 18.0
    32151602
  • Protection class
    III (IEC 61140, EN 61140, VDE 0140-1)
  • Immunity to ESD
    Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
  • Immunity to conducted interference
    Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
  • Immunity to surge
    Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric), ±1 kV on unshielded I/O cables
  • ECLASS 10.0.1
    27242608
  • ECLASS 11.0
    27242608
  • UNSPSC 21.0
    32151602
  • UNSPSC 20.0
    32151602
  • ETIM 3.0
    EC001604

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

Shipping and Delivery Worldwide

calculate cost and time at Checkout


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo