Nikki Gonzales
Nick Goetz
Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

2688433 Phoenix Contact Programmable Logic Controllers

Phoenix Contact 2688433 Axioline F function module, 1 SSI interface for absolute encoder, 1 analog output: 0 - 10 V, ±10 V, 0 - 5 V, ±5 V, 0 - 20 mA, 4 - 20 mA, ±20 mA, 2-conductor connection technology (including bus base module and connectors)
Phoenix Contact

Part#:2688433

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: Axioline F function module, 1 SSI interface for absolute encoder, 1 analog output: 0 - 10 V, ±10 V, 0 - 5 V, ±5 V, 0 - 20 mA, 4 - 20 mA, ±20 mA, 2-conductor connection technology (including bus base module and connectors)

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Programmable Logic Controllers that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2688433 Phoenix Contact price in the box on the right side or send a quick quote.

2688433 Product Details

  • Air pressure (operation)
    70 kPa ... 106 kPa (up to 3000 m above sea level)
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section AWG max.
    16
  • Note on weight specifications
    with connectors and bus base module
  • Supply voltage
    24 V DC
  • Protective circuit
    Surge protection electronic (35 V, 0.5 s)
  • Parity
    Even, odd or no parity
  • Current carrying capacity
    max. 500 mA
  • Data formats
    IB IL, S7-compatible, standardized representation
  • Voltage output signal
    0 V ... 5 V
  • Immunity to EF
    Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 5.0
    27242200
  • ECLASS 9.0
    27242605
  • UNSPSC 11
    39121311
  • UNSPSC 18.0
    32151602
  • Conductor cross section solid max.
    1.5 mm²
  • Stripping length
    8 mm
  • Mounting position
    any (no temperature derating)
  • Current consumption
    max. 60 mA (Supply of the SSI interface and the analog output (20 mA), without sensor supply)
  • Input name
    SSI interface
  • Encoder signals
    Single-turn and multi-turn encoder, length measuring sticks
  • Adjustable resolution
    8 ... 56 bit
  • Connection technology
    2-conductor (shielded, twisted pair)
  • Representation of output values
    16 bits (15 bits + sign)
  • Current output signal
    0 mA ... 20 mA
  • Protection class
    III (IEC 61140, EN 61140, VDE 0140-1)
  • ECLASS 10.0.1
    27242605
  • ECLASS 5.1
    27242600
  • ECLASS 6.0
    27242600
  • UNSPSC 6.01
    43172015
  • UNSPSC 20.0
    32151602
  • Designation
    Feed-in of supply voltage (UI)
  • Conductor cross section AWG min.
    24
  • Degree of pollution
    2 (IEC 60664-1, EN 60664-1)
  • Supply voltage range
    19.2 V DC ... 30 V DC including all tolerances, including ripple
  • Nominal output voltage
    24 V DC (UI - 0.5 V)
  • Number of outputs
    1
  • D/A converter resolution
    16 bit
  • Measured value representation
    16 bits
  • Permissible cable length
    max. 250 m
  • Immunity to burst
    Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
  • Interference emission
    Noise emission test according to EN 61000-6-3 Class B
  • Overvoltage category
    II (IEC 60664-1, EN 60664-1)
  • ECLASS 4.0
    27240400
  • UNSPSC 7.0901
    43201404
  • UNSPSC 12.01
    39121311
  • UNSPSC 21.0
    32151602
  • Voltage range
    19.5 V DC ... 30 V DC (including all tolerances, including ripple)
  • Output name
    Analog outputs
  • Load/output load current output
    max. 500 Ω
  • Air pressure (storage/transport)
    70 kPa ... 106 kPa (up to 3000 m above sea level)
  • Conductor cross section flexible max.
    1.5 mm²
  • Color
    traffic grey A RAL 7042
  • Transmission speed
    100 Mbps
  • Power consumption
    max. 1.4 W (Supply of the SSI interface and the analog output (20 mA), without sensor supply)
  • Input frequency
    to 2 MHz (Can be parameterized: 67.5 kHz, 125 kHz (default), 250 kHz, 500 kHz, 1 MHz, 2 MHz)
  • Test section
    Logic 500 V AC 50 Hz 1 min.
  • Mechanical tests
    Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
  • ECLASS 11.0
    27242605
  • UNSPSC 13.2
    32151602
  • Protective circuit/component
    Electronic (35 V, permanent)
  • Precision
    typ. 0.1 % (of output range final value)
  • Load/output load voltage output
    > 2 kΩ
  • Degree of protection
    IP20
  • Connection method
    Push-in connection
  • Conductor cross section flexible min.
    0.2 mm²
  • Mounting type
    DIN rail
  • Net weight
    135 g
  • Number
    2
  • Number of inputs
    1
  • Encoder supply voltage
    24 V DC (UI - 0.5 V)
  • Type of protection
    Surge protection
  • D/A conversion time
    5 µs
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.1
    27240400
  • ETIM 4.0
    EC001601
  • ETIM 7.0
    EC001601
  • UNSPSC 19.0
    32151602
  • Height
    126.1 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Description of the input
    RS-422 interface according to SSI specification
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • Immunity to conducted interference
    Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
  • Width
    35 mm
  • Ambient temperature (operation)
    -25 °C ... 60 °C
  • Depth
    54 mm
  • Immunity to ESD
    Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
  • Note on dimensions
    The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
  • Permissible humidity (storage/transport)
    5 % ... 95 % (non-condensing)
  • Note on the connection method
    Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
  • Transmission frequency
    2 MHz
  • Immunity to surge
    Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), ±1 kV to shielded I/O cables
  • ETIM 6.0
    EC001601
  • ETIM 3.0
    EC001599
  • ECLASS 7.0
    27242605

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2688433

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty