The 3-phase and 1-/2-stage EMC filters MEF 3/1-3/2 are used in the range 0.1...30 MHz and dampen interferences found in cables from the mains, supply units and control systems. They are suitable for TN-C-mains. The best results are obtained with short con
Dimensions H×W×D
250×90×100 mm
Connection
Screw connection, touch protected
Climatic category
25/085/21 (EN 60068-1)
Operating voltage
max. 3× 600 V AC
Test isolation voltage
3.3 kV (L-N), 2 s; 3.1 kV (L-L), 2 s
Overload current
18× (IN t) max. 0.5 ms; 1.5× (IN t) max. 1 min. (1× per hour)